Three-phase AC Protection Box GAVE ACT63SDA/300 44kW 63A 300mA
Modelo: ACT63SDA/300- Sku: GAVEPRO010
- Vendor: GAVE
Specifications
Product Description
The GAVE ACT63SDA/300 44kW 63A 300mA Three-Phase AC Protection Box is a turnkey 3F+N panel designed to protect and connect, with maximum reliability, high-flow AC branches in three-phase installations. It integrates, in a single polycarbonate enclosure with double insulation (Class II) and IK08, a four-pole 63 A circuit breaker, a Type A selective 300 mA residual current device—ideal for fire protection and to ensure selectivity with downstream RCDs—and a Type II surge protection device (SPD). With this configuration, the panel reduces installation time, organizes wiring, and ensures technical compliance in self-consumption, backup, or light/medium C&I systems up to ~44 kW.
Main Features
- Electrical capacity: up to 63 A per phase (≈ 43.6–44 kVA/kW at 3×400/230 V, 50 Hz).
- 4P 63 A circuit breaker (MCB), curve C, 6 kA breaking capacity according to EN 60898-1.
- 4P Type A 300 mA selective RCD, immune to unwanted tripping (EN 61008-1).
- Type II SPD (In 20 kA, Imax 40 kA, Up 1.5 kV) with associated fuse (EN 61643-11).
- Class II polycarbonate enclosure, high impact resistance IK08, suitable for protected outdoor use.
- Streamlined internal wiring and DIN rail for quick, clean, and maintainable installation.
Advantages or Benefits
- Selectivity and service continuity: the 300 mA (S) RCD reduces nuisance tripping, protects against fire risk, and maintains selectivity with 30 mA RCDs in subpanels.
- Integrated safety: circuit breaker, RCD, and SPD in the same panel protect people and equipment against overloads, indirect contact, and network transients.
- Agile and orderly installation: fewer field connections, accessible terminals, and clear labeling shorten commissioning and facilitate maintenance.
- Technical compliance: switchgear and construction in accordance with IEC/EN standards, facilitating audits and legal certification of installations.
- Robustness and durability: quality materials, double insulation Class II, and IK08 for demanding environments (indoor or protected outdoor).
Purpose or Applications
Designed to act as an interconnection and safety point between AC generation/backup and the main panel in high-power three-phase installations. Its use is ideal in advanced residential self-consumption, tertiary, and light/medium C&I, with string inverters of 30–40+ kW or branches of three-phase microinverters, as well as in systems with AC-coupled batteries when the line current does not exceed 63 A/phase. It is also suitable for schemes with export limitation and energy monitoring via CT or external meters.
Technical Specifications
| Power | ≈ 44 kW (63 A/phase at 3×400 V) |
| Nominal voltage | 3×400/230 V~ · 50 Hz (three-phase 3F+N) |
| Format | Polycarbonate enclosure · Class II (double insulation) · IK08 |
| Circuit breaker protection | 4P 63 A · curve C · 6 kA (EN 60898-1) |
| RCD protection | Type A · 300 mA · 4 poles · selective S (EN 61008-1) |
| SPD | Type II · In 20 kA · Imax 40 kA · Up 1.5 kV · with fuse (EN 61643-11) |
| Circuits | 1 dedicated three-phase AC circuit |
| Dimensions | ≈ 286 × 418 × 148 mm (height × width × depth) |
Compatibilities
Compatible with three-phase inverters of 30–40+ kW and with 3F microinverter branches, provided the aggregate does not exceed 63 A/phase. It can be integrated with monitoring systems (CT/meters), selectivity with IGA and 30 mA RCDs in subpanels, and coordination with main SPD according to project and local regulations.
GAVE ACT63SDA/300 44kW 63A 300mA Three-Phase AC Protection Box is a professional solution for demanding projects: it provides comprehensive safety, differential selectivity, panel organization, and reliability at the AC interface, optimizing installation times and protecting equipment and people from day one.
Have a question?