Type B Residual Current Device 4P 40A 30mA Tongou TORD4B-63

Modelo: TORD4B-63 Tipo B 4P 40A 30mA
  • Sku: TONGPRO009
  • Vendor: Tongou
€112,16 EUR
€84,12 EUR
 per 
Tax included.
Shipping calculated at checkout.
In stock!
Spend €150,00 to FREE SHIPPING

The Differential Type B 4P 40A 30mA Tongou TORD4B-63 protects three-phase networks with AC, pulsating DC, and pure DC detection. 380–415 V, 50 Hz, 6 kA cond., IP40/20, 8 modules, terminals up to 35/25 mm² and torque 2.5 Nm. DIN.

Purchase with Secure Payment

Specifications

Product Description

The Diferencial Tipo B 4P 40A 30mA Tongou TORD4B-63 is a four-pole RCCB for three-phase installations with power electronics, such as electric vehicle chargers, photovoltaic inverters on the grid side, or variable frequency drives. Class B ensures operation against residual sinusoidal (AC), pulsating (type A), and pure direct current leaks, preventing the saturation that renders conventional RCCBs ineffective. With a nominal 40 A and 30 mA sensitivity, it ensures personal protection and reduces fire risk in residential, tertiary, and light industrial panels.

Main Features

  • True Class B according to IEC/EN 62423: detection of AC, A, and smooth DC.
  • 4P, 40 A, 30 mA, 380–415 V, 50 Hz; modular format for 35 mm DIN rail.
  • Conditional short-circuit capacity: 6 kA; Ui 250 V; Uimp 6 kV.
  • IP40 (device) / IP20 (terminals) ratings; width 8 modules (≈71.6 mm).
  • Terminals: rigid 1–35 mm² and with ferrule/flexible 1–25 mm²; tightening torque 2.5 Nm.
  • Durability: 20,000 mechanical and 15,000 electrical operations; max altitude 2000 m.

Advantages or Benefits

  • Complete three-phase safety in the presence of harmonics and DC component.
  • Service continuity with lower tendency to unwanted tripping.
  • Compact and tidy installation: 8 steps, clear signaling, and wide terminals.
  • Complies with EN/IEC 61008-1 and IEC/EN 62423 for professional projects.
  • Simple maintenance with front access and ferrule recommendation.

Purpose or Applications

Recommended for three-phase wallbox units, EV subpanels, AC self-consumption, HVAC, and pumping with variable frequency drives. Optimal when the manufacturer requires class B or there is a risk of residual DC injection.

Technical Specifications

Type RCCB Type B
Poles / Current 4P / 40 A
Sensitivity 30 mA
Voltage / Frequency 380–415 V AC / 50 Hz
Conditional capacity 6 kA
Ui / Uimp 250 V / 6 kV
Cable section Rigid 1–35 mm² | With ferrule 1–25 mm²
Tightening torque 2.5 Nm
Degree of protection IP40 (module) / IP20 (terminals)
Operating temperature −25 °C…+60 °C | Storage −40 °C…+85 °C
Operating altitude Up to 2000 m
Modular width 8 × 9 mm (≈71.6 mm)
Dimensions (H × D) ≈85 × 75.1 mm
Mounting 35 mm DIN rail
Standards EN/IEC 61008-1 · IEC/EN 62423

Compatibilities

Use with three-phase EV chargers, AC inverters, and variable frequency drives. Complete with main 40 A circuit breakers, modular watertight enclosures, and copper ferrules/terminals for professional wiring.

The Diferencial Tipo B 4P 40A 30mA Tongou TORD4B-63 offers robust, compact, and standards-compliant class B three-phase protection.

PDF Icon Descargar ficha técnica View full details

Type B Residual Current Device 4P 40A 30mA Tongou TORD4B-63

€112,16 EUR
€84,12 EUR
 per 

Recently viewed